RFL SMX3/40 Page 10 of 24 Issue 2.02
User Manual
07 May 2009
9. V24 ports
Four DCE ports are provided on DB9 female connectors for asynchronous data:
Circuit Pin Direction
TxD Transmit Data 3 Input
RxD Receive Data 2 Output
RTS Request to Send 7 Input
CTS Clear to Send 8 Output
DCD Data Carrier Detect 1 Output
DTR Data Terminal Ready 4 Input
DSR Data Set Ready 6 Output
RI Ring Indicator 9 Output
SG Signal Ground 5
Screen / Drain must be connected to the connector Shell
RI is permanently OFF.
DSR is ON when aggregate framing is synchronised.
DTR is ignored.
RTS turns on remote DCD and local CTS after a delay.
Transceivers are specified to ± 15kV IEC1000-4-2 air discharge ESD protection and
port connections are additionally protected by Tranzorb type arrays.
DIP switches provide configure options for each port, see section 10.
Data Channel Concatenation
SMX3/40 units co-located at one end of adjacent unsynchronised links may be
concatenated at the V24 level either through the connected equipment, or directly
using a crossed RS232 data cable.