RFL SMX3/40 Page 18 of 24 Issue 2.02
User Manual
07 May 2009
Example 2: Aggregate Concatenation with synchronised links (e.g. SCADA
network on two BT kilostream X21 links):
Set Aggregate Direction for A2 and C1 to X21 port, and for B1 and B2 to Both
ports. Transmit and Receive data is presented at all ports. Only possible on a well
disciplined system, where only one terminal transmits at once. This configuration
assumes that both X21 links are running on the same network master clock e.g.
BT Kilostream.
DIP Switch Settings for units A2, C1
8 7 6 5 4 3 2 1
SW1 * * * * * * * *
SW2 0 1 0 0 1 0 0 1
SW3 * * * * * * * *
SW4 * * * * * * * *
SW5 0 0 0 0 0 0 0 1
SW6 0 0 0 0 * * 1 *
* indicates setting not applicable to this setup
DIP Switch Settings for units B1, B2
8 7 6 5 4 3 2 1
SW1 * * * * * * * *
SW2 0 1 1 0 1 0 0 1
SW3 * * * * * * * *
SW4 * * * * * * * *
SW5 0 0 1 1 0 0 0 1
SW6 0 0 0 0 * * 1 *
* indicates setting not applicable to this setup
Substation A Substation B Substation C
BT X21 BT X21
Aggregate Concatenation
C1 B2B1A2
V24
Port 2
V24
Port 2
V24
Port 2
V24
Port 2
Aggregate channel: V24 port 2 on each unit is allocated to channel B, baud rate 2400
Example installation – SCADA network