RFL SMX3/40 Page 17 of 24 Issue 2.02
User Manual
07 May 2009
14. Example Configurations
Example 1: Point to point: asynchronous data: minimal delay (eg protection
relays):
Set Aggregate Direction for A2, B1, B2 and C1 all to X21 port. Data from B1 will
communicate to A2 on aggregate channel A; separate data will be communicated
from B2 to C1 using the same aggregate channel. This configuration assumes a
master clock signal is provided by the X21 links.
DIP Switch Settings for all units
8 7 6 5 4 3 2 1
SW1 0 0 0 0 0 1 0 0
SW2 * * * * * * * *
SW3 * * * * * * * *
SW4 * * * * * * * *
SW5 0 0 0 0 0 0 0 1
SW6 0 0 0 0 * * * 0
* indicates setting not applicable to this setup
Substation A Substation B Substation C
X21 X21
C1 B2B1A2
V24
Port 1
V24
Port 1
V24
Port 1
V24
Port 1
Aggregate channel: V24 port 1 on each SMX3/40 is allocated to channel A
Example installation – Two RS232 Protection Links